contact us
REPSUN LIGHTNING PROTECTION CO., LIMITED
We provide customers with quality products and provide high-quality services.
If you would like to leave us a comment please go to contact us
PRODUCTS DETAIL
Product Picture
(L-N/PE)
(N-PE)
(1+1)
(2+0)
(3+0)
(3+1)
(4+0)
Dimension drawing(mm)2P
Basic circuit diagram
Features
Type2 surge protector SPD;
Fast response(≤25ns); low protection level (≤2.0kV);
Reliable safety due to double integrated disconnectors with double protections;
Optional to use without a back up fuse
Failure indication window, remote alarm terminal optional
Datasheet
Type |
REP-MP60T2-XXX-XS |
||||
The SPD according to IEC/EN 61643 |
II/T2 |
||||
Maximum continuous vottage Uc[L-N] |
440Vac |
385Vac |
320Vac 275Vac |
150Vac |
|
Maximum continuous voltage Uc [N-PE] |
255Vac |
||||
Nominal discharge current(8/20μs )ln |
60kA |
||||
Maximum discharge currenl(8/20μs )lmax |
120kA |
||||
Voltage protection level Up [L-N] |
≤2.7kV |
≤2.5kV |
≤2.3kV |
≤2.0kV |
≤1.8kV |
Voltage protection level Up [N-PE] |
<1.8kV |
||||
Response time |
25ns[L-N/PE]/100ns[N-PE] |
||||
Operating temperature range |
-40°C~+80°C | ||||
The minimum cross-sectional area of installation |
1.5mm² solid/flexible |
||||
The maximum cross-sectional area of installation |
25mm² solid/flexible |
||||
Remote alarm contact |
Remote alarm contact optional |
||||
Degree of protection |
IP20 |
||||
Failure indication |
Green: Normal ; Red: Failure |
||||
Enclosure material |
Thermoplastic; extinguishing degree UL94-V0 |
||||
Technical feature |
Double integrated disconnection devices with double protections |
Request A Quote